How does a diesel generator room located in a basement pass the fire department inspection?

July 05, 2022
Diesel generator set as an important power supplement, in addition to special mobile trailer power station, outdoor rain shed generator, silent generators, such as a small number of outdoor use, most of the ordinary open-frame diesel generators need to set a generator room attentively placed diesel generator set, the general diesel generator room is arranged in the first floor or underground 1, 2 floors, then placed in the basement of the diesel generator room how to Through the fire department's acceptance?
Diesel generator room
 
Diesel generator set as an important power supplement, in addition to special mobile trailer power station, outdoor rain shed generator, silent generators and other small part of the outdoor use, most of the ordinary open-frame diesel generator set need to set a generator room attentively placed diesel generator set, the general diesel generator room are arranged in the first floor or underground 1, 2 floors, then placed in the basement of the diesel generator room how to Through the fire department's acceptance?
 
1, diesel generator room should be used fire resistance limit of not less than 2.00h partition walls and 1.5h floor slab and other parts of the separation.
 
2, high-rise buildings, diesel generator room should be set up in the storage room, the total storage capacity should not exceed 8.00h needs, or daily fuel tank volume of not more than 1m3. storage room should be separated from the generator using a firewall; when the firewall must open the door, should be set to close the Class A fire doors.
 
3, diesel generator room is arranged in non-high-rise buildings, diesel generator room and daily fuel tank room fire resistance level of one.
 
4, should be set up automatic fire alarm system and automatic fire extinguishing system.
 
5, diesel generator room and control room lighting branch line should be connected to the fire distribution circuit.
 
6, the engine room must be equipped with fire-fighting equipment, such as: oil fire extinguishers, dry powder fire extinguishers and gas fire extinguishers.
 
7、The machine room is equipped with fire hydrant, fire belt and fire hose outside.
 
8, the engine room should be equipped with a prominent no fire and smoke safety icons, and prohibit fire and smoke text.